TECHNICAL

Fixed Pattern

SPECIFICATIONS

TESTING /

CERTIFICATION

TEST LABS

- Fixed pattern up to 3200A incomer.
- Withdrawable up to 3200A incomer.
- Top or bottom entry / exit.
- Rear power terminal section or cableway tier.
- 50kA/1s Fault LVL.
- All incoming and outgoing devices from 400-3200A, are designed with termination kit.
- 690V insulation rating (switchgear component limit).
- 1000V insulation rating (incomer and busbar systems).
- Tested for South African voltage requirement of 400V +/- 10% @ 50HZ
- IP 3X rated.
- Square key latches on door (every door to have one latch lockable).
- Form 3b separation.
- Access covers on rear secured with screws.
- Termate busbar support system.
- Merlin Arc Pressure Valve (MAPV).
- Selection charts based on modules.
- Modular design allows for future extension on all assemblies.
- IEC 61439-2 certified
- ASTA accredited.
- Meets and exceeds:
SANS: 1973-1 (Assemblies above 10kA)
1973-3 (Assemblies 10kA and below)
1973-8 (Minimum tested assemblies above 10kA and less than 1600A)
(Note: SANS standard makes reference to 604391, which has been withdrawn by IEC and replaced with IEC 61439-1 & 2. Testing to IEC 61439-2 exceeds testing done to 60439-1.)
- ARC containment to IEC/TR61641
- kA testing facility (UK)
- IPH Berlin (Germany)
- Prof. Ir. Damstra Laboratory (Netherlands)
- Netfa (SA) (arc containment test only)

Panel Builders

PANEL BUILDERS,

CONSULTANTS AND

CLIENT/END USERS

Recommend rear access of 800mm with a minimum of 600mm for completely isolated panels.
- Operational front access of 1200mm
- All panels are supplied with the option of extension on either end.
- All shipped sections can be moved / rigged with standard 2,5T forklift.
- Merlin Arc Pressure Valve (MAPV) requirement to be advised at time of quote / order.
- Standard heavy-duty base of 3mm mild steel welded construction and powder coated black.
- Frame, covers and chassis plates made of Aluzinc, giving good bonding properties with powder coating optional.
- Gland plates of 2,5mm galvanized plates as standard, 3mm galvanized and 5mm aluminium is optional.
- Doors and covers standard colours: light grey or orange. Additional colour options available.
- We recommend using ACB’s for main incoming and any outgoing circuit of 800A, 1000A, 1250A, 1600A, 2000A, 2500A and 3200A.
- IP3X recommended for internal panels as higher IP ratings cause switchgear components to operate at higher temperatures thus reducing the service life.

M280

M280 - INDOOR

TYPE SINGLE DOOR

CONSTRUCTION

M280 - OUTDOOR TYPE DOOR CONSTRUCTION

TESTING / CERTIFICATION

- 2.5 mm galvanised gland plates top and bottom
- Bolt on outer door hinge to allow easy replacement
- Optional inner door fitted to body
- Aluzinc 2mm chassis plate
- Earth stud on all doors
- Door latches with 3 mm steel cam and square key
- Outer door to be fitted with one barrel type latch to allow locking
- Colour options of orange, light grey, red and white
- 280 mm of useable depth measured inside the enclosure
- 2.5 mm galvanised gland plates bottom only
- Weatherproof canopy
- Double door construction with adjustable inner door (where inner door is required)
- Optional inner door fitted to body
- Bolt on outer door hinge to allow easy replacement
- Aluzinc 2mm chassis plate
- Earth stud on all doors
- Door latches with 3 mm steel cam and square key
- Outer door to be fitted with one barrel type latch to allow locking
- Colour options of light grey or orange
- 280 mm of useable depth measured inside the enclosure
- Optional louvred door where high heat loads are expected
- Tested to IP55 – Test certificate TR2335/13-049